5.1 Nature of information
The following information shall be given by the manufacturer:
ldentification
a) The manufacturer’s name or trade mark.
b) A type designation or serial number that makes it possible to get the relevant information concerning the switching element (or the entire control switch) from the manufacturer.
c)“IEC 60947-5-8″ if the manufacturer claims compliance with this standard.
d) Three- position enabling switches shall be indelibly and legibly marked by the symbol:
NOTE If it is not possible to affix the marking to the switch due to size constraints, then the symbol may be put in the instructions for installation, operation and maintenance.Basic rated values and utilization
e) Actuating forces and operational stroke.
f) Rated operational voltages (see 4.3.1.1 of IEC 60947-5-1).
g) Uilization category and rated operational currents at the rated operational voltages of the switching element.
h) Rated insulation voltage (see 4.3.1.2 of IEC 60947-5-1).
i) Rated impulse withstand voltage Uimp in accordance with 4.3.1.3 of IEC 60947-1.
a) j) IP code (see 5.1 and Annex C of IEC 60947-1).
k) Pollution degree (see 6.1 .3.2 of IEC 60947-5-1).
I) Type and maximum ratings of short-circuit protective device (see 8.3.4.3 of IEC 60947-5-1).
m) Conditional short-circuit current if less than 1 000 A.
n) Indication of contact elements of same polarity.
o) Mechanical and/or electrical durability.
5.2 Marking
5.2.1 General
Marking of data specified in items a), b), c) and d) of 5.1 is mandatory on the nameplate of the three-position enabling switch in order to permit the complete information to be obtained from the manufacturer.
Marking shall be indelible and easily legible, and shall not be placed on screws and easily removable parts.
Whenever space permits, data under items e) to 0) of 5.1 shall be included on the nameplate,or on the three-position enabling switch or otherwise in the manufacturer’s published literature.
5.2.3 Functional markings
To avoid confusion with emergency stop devices, the actuator of an enabling switch shall not be coloured RED (see also IEC 60204-1).
5.3 Instructions for installation, operation and maintenance Subclause 5.3 of IEC 60947-1 applies.
5.4 Additional information
Subclause 5.4 of IEC 60947-5-1 applies.
6 Normal service, mounting and transport conditions
Clause 6 of IEC 60947-1 applies with the following additions.
6.1.3.2 Pollution degree
Unless otherwise stated by the manufacturer, a three- position enabling switch is intended for installation under environmental conditions of pollution degree 3. However, other pollution degrees may apply, depending upon the micro-environment.
6.3 Mounting