UL-1479:2015 pdf free download – STANDARD FOR SAFETY Fire Tests of Penetration Firestops

02-19-2022 comment

UL-1479:2015 pdf free download – STANDARD FOR SAFETY Fire Tests of Penetration Firestops.
5.1.1.3 Penetrating items of horizontal assemblies are to be exposed to the furnace temperatures for the minimum specified distance of 11 in (279 mm) from the plane representing the bottom surface of a floor assembly or floor-ceiling assembly and shall not be contained within the cavity of a wall under test conditions regardless of whether the intended application involves a completely exposed penetrant or one which may be fully or partially contained within the cavity of a wall.
5.1.1.4 The periphery of the test sample is to be not closer than 1-1/2 times the thickness of the test assembly, or a minimum of 12 in (300 mm), to the furnace edge, whichever is greater. The distance between the test sample periphery and furnace edge can be reduced if it is demonstrated that the edge effects do not affect the test results.
5.1.2 Membrane-penetration firestop systems for other than outlet boxes
5.1.2.1 For membrane-penetration firestop systems for other than outlet boxes, the penetrations and supporting construction to be tested shall be representative of the construction for which ratings are desired with respect to materials, workmanship, and details such as dimensions of parts. The membrane-penetration firestop system is to be installed in accordance with the manufacturer’s specified installation instruction procedure.
5.1.2.2 Each representative construction type of membrane-penetration firestop system for which rating is desired is to be tested. The membrane-penetration system, other than metallic outlet boxes, shall be evaluated with the firestop system exposed to the furnace condition and also a second configuration with the firestop system facing away from the furnace, If it is determined by the testing laboratory that one exposure is representative of both exposures, the testing laboratory shall test that one exposure.
5.1.3 Membrane-penetration firestop systems for outlet boxes
5.1.3.1 For membrane-penetration firestop systems for outlet boxes, the penetrations and supporting construction to be tested shall be representative of the type construction for which ratings are desired with respect to materials, workmanship, and details such as dimensions of parts. The membrane-penetration firestop system for outlet boxes is to be installed in accordance with the manufacturer’s specified installation instruction procedure.
5.1.3.2 Unless a different rating is desired for a different construction scheme, the outlet boxes are to be installed in the test sample which is minimum 48 in (1219 mm) in width as indicated in Figure 5.2. The exposed surface shall contain one receptacle outlet box with faceplate positioned at the height of 12 in (305 mm) from the bottom of the test assembly. The unexposed surface shall contain one outlet box with faceplate and one switch outlet box with faceplate. The exposed surface outlet box and the unexposed surface outlet box shall be located at the same level in the assembly with the maximum 24 in (610 mm) space and interconnected with the appropriate conduit. The switch outlet box shall be located at a maximum of 32 in (813 mm) above the exposed outlet box and interconnected with the appropriate wiring, conduit and associated hardware. Unless otherwise specified, all boxes shall be secured to framing members.

Main Focus Download
UL-62841-2-5:2016 pdf free download – STANDARD FOR SAFETY Electric Motor-Operated Hand-Held Tools, Transportable Tools And Lawn And Garden Machinery – Safety一Part 2-5: Particular Requirements for Hand-Held Circular Saws UL Standards

UL-62841-2-5:2016 pdf free download – STANDARD FOR SAFETY Electric Motor-Operated Hand-Held Tools, Transportable Tools And Lawn And Garden Machinery – Safety一Part 2-5: Particular Requirements for Hand-Held Circular Saws

UL-62841-2-5:2016 pdf free download - STANDARD FOR SAFETY Electric Motor-Operated Hand-Held Tools, Transportable Tools And Lawn And Garden Machinery - Safety一Part 2-5: Particular Requirements for Hand-Held Circular Saws. NOTE For circular saws with a maximum blade diameter...
More
UL-62133:2017 pdf free download – STANDARD FOR SAFETY Secondary Cells and Batteries Containing Alkaline or Other Non-Acid Electrolytes – Safety Requirements for Portable Sealed Secondary Cells, and for Batteries Made From Them, for Use in Portable Applications UL Standards

UL-62133:2017 pdf free download – STANDARD FOR SAFETY Secondary Cells and Batteries Containing Alkaline or Other Non-Acid Electrolytes – Safety Requirements for Portable Sealed Secondary Cells, and for Batteries Made From Them, for Use in Portable Applications

UL-62133:2017 pdf free download - STANDARD FOR SAFETY Secondary Cells and Batteries Containing Alkaline or Other Non-Acid Electrolytes - Safety Requirements for Portable Sealed Secondary Cells, and for Batteries Made From Them, for Use in Portable Applications....
More

LEAVE A REPLY

Anonymous netizen Fill in information